First Assistance
Battery off-
- Switch battery on.
 - Listen for a latching sound, and the latching relay must close.
 - Measure power on terminals of battery while battery is not connected to anything else.
 - Is the screen on of the battery?
 - Look for error codes. If error codes are present, please follow the guides instructed in the manual.
 - If there are no errors and there is still no power on terminals, contact your installer or supplier.
 - If the screen is dead, please contact your installer or supplier.
 
No CAN-bus Communication
- Please contact your installer or supplier.
 - Please follow the guides on our knowledge base.
 - https://desk.zoho.com/portal/bluenova/kb/bluenova
 
VCell Low.
- Check all the cell voltages, and there will be a cell with a lower cell voltage than the rest of the cells.
 - If you have a cell lower than 1.8V, must the battery be sent back to Blue Nova Energy for cell revival.
 - Those cells need to be charged to the same voltage values as the rest.
 - You can charge the total pack from an inverter with a low current of about 5ah max until all the cells are above 3.5V and bleeding.
 - Leave these settings for about a week. 
 - Set the bulk voltage to the following settings.
56.5V 5A for a 48V system.
28.1V 5A for a 24V system.
14.V 5A for a 12V system.
If you are not able to do this or it does not solve your problem, please contact your supplier or installer. - If this is a regular problem, please use an Equalisation Function. Set to equalize at least every seven days for 120 mins to the following voltage.
 
57.5V 5A for a 48V system.
28.8V 5A for a 24V system.
14.5V 5A for a 12V system.
VCell High.
- Check all cell voltages, and there will be a cell with Higher voltages than the rest of the cell.
 - Those cells need to be charged to the same voltage values as the rest.
 - You can charge the total pack from an inverter with an low current about 5Amax until all the cells are below 3.51V.
 - Set pack to following settings.
55.5V 5A for a 48V system.
27.5V 5A for a 24V system.
13.5V 5A for a 12V system.
If you are not able to do this or it does not solve your problem, please contact your supplier or installer. 
Cell comm Error.
- Confirm that battery is correctly connected up, As per in user manual. 
 - Confirm data and coms connections as per user manual. 
 - Make sure you have the latest firmware installer BMMC V3.5 / 123BMS V5.12.
 - Check that all the cells of the battery are above 3V if not override that battery and charge the pack.
 - Please contact your supplier or installer.
 
Dead or Flat Battery.
- Switch battery on look if the display will boot up go to override, hold the button in until override is active, and until you see a positive current going into the battery.
 - If this is not possible, jump-start your battery to get the display active, and follow the same process as in no 1. (WARNING When you jump-start the battery make sure you remove the external battery before the contactor close)
 - If nothing is working, please contact your installer or supplier.
 
If your installed or supplier can not assist, please log a ticket via the following link.
https://desk.zoho.com/portal/bluenova/newticket