Guide to a healthy and happy battery
Dear BlueNova Energy client, the following guide will assist you to maintain your battery in a healthy manner and to prevent unnecessary maintenance on your system.
Directions
Setpoints for voltage-based setup:
For installations that exclude serial/CAN communication, set the following values:
13V | 26V | 39V | 52V | |
V(high set) / Bulk / Absorb | 14.1V | 28.1V | 42.1V | 56.2V |
V(float) | 13.9V | 27.8V | 41.6V | 55.5V |
V(reconnect) | 12.8V | 25.6V | 38.4V | 51.2V |
V(low set) | 12.0V | 24.0V | 36.0V | 48V |
Notes:
Support:
For any technical assistance, please log a ticket on our support system.
https://www.bluenova.co.za/contact-us/support/
Supporting materials:
Supporting documents, latest firmware, and manuals can be found on our website under the knowledge base.(BlueNova-contact us-support-login-knowledgebase)
https://desk.zoho.com/portal/bluenova/home
Contact information:
BlueNova Technical Support +27(0)21 205 2000 / support@bluenova.co.za
We value your feedback! For suggestions on how we can improve our products
and services, please email BlueNova Customer Care at feedback@bluenova.co.za